In this dialog box, you can edit the specific parameters for a connection to Mitsubishi Melsec-Q PLCs.
You need to set these parameters if a Mitsubishi Net has been set up and the hardware supports it.
Routing
|
Description
|
Hex
|
Decimal
|
Network Number
|
Network ID in the hardware configuration of the programming software
|
0
|
0
|
PC Number
|
Only relevant if a permission management system has been set up, allowing or denying PC access.
|
0xFF
|
255
|
Destination Module IO Number
|
Network address
|
0x3FF
|
1023
|
Monitor Timer
|
Monitors the time within which the response should be received.
|
0x100
|
256
|
Destination Module Station Number
|
Module address of another module in a PLC.
|
0
|
0
|
Monitoring Timer
0 for infinite, or a timeout in units of 250 ms.
The effect of these values depends on the hardware used.
|