Modbus protocol settings

Home  Back  Next

In this dialog box, you can edit the specific parameters for the connection to Modbus PLCs.

 

 

Description

Default

Name of the Connection

This field displays the connection name which can be changed here.

 

Slave address

The slave address entered here will be transmitted in the Modbus frame.

9

Start Address 0

The starting address in the frame will be transmitted as specified.

Yes

Start Address 1

Some Modbus devices expect a starting address in the frame that is 1 less than the one you entered. The first address is 1.

No

Use Byte Swap

Swaps the bytes within a word

Off

Use Word Swap

Swaps the words within a double word (32 bits)

Off

Output Write

For writes, the Modbus opcode “Write Single Coil 05” is used or “Write Multiple Coils 15” or both

both

Register Write

For writes, the Modbus opcode “Write Single Register 06” is used or “Write Multiple Registers 16” or both

both

Register Bitwrite

Nearly all Modbus devices are supporting the register bitwrite using opcode 22. For devices without this an insecure version can be used: Read a register, modify a bit and write the register back.

Opcode 22

 

The slave address will be indicated in the item syntax.

Example: Id2.R2

For more details, see Modbus Item Syntax